The following is submitted by Dick Albritton
A/C OPERATIONAL TESTS
BY
DICK ALBRITTON
TEMPERATURE DIFFERENCE TEST
These tests should be run with outdoor temps. above 80 degrees and the
Site Selector Switch in the 50 position. The thermostat should be set
at least 10 degrees below the indoor temperature to be sure both
compressors are being signaled to run and the unit should be allowed to
run without cycling for 10 to 15 minutes with fan speed on high before
taking readings. The thermometers should read within 1 degree of each
other. Place one thermometer or probe at the return air filter
location, place the other in a bedroom floor grill.
Take readings and calculate the difference. The difference should be
19 degrees or more depending on the environmental conditions.
Anything much different from this indicates problems. -- Have system
checked.
ELECTRICAL AMPERAGE TEST
To do this test you will need a clip on amp meter. Again, set the
thermostat down at least 10 degrees and let the unit run for 10 minutes
before taking measurements.
Remove the main electrical panel cover. Take amp draw readings of A/C
#1 and A/C #2 circuits. Depending on the environmental conditions, the
readings should be 11 to 14 amps. Also there should be a difference of
1 to 2 amps between the 2 readings due to a difference in the amp draw
of the 2 blowers.
If one the readings is 7 to 10 amps then there is probably trouble with
that section of the unit.
ARE BOTH UNITS RUNNING?
This simple check is probably the 1st one that should be done.
With the thermostat OFF and the A/C unit has been OFF for 5 minutes,
set the desired temperature 10 degrees below indoor temperature. Set
the switch to COOL. Now go directly outside beside the A/C unit. You
should hear the unit running. In approximately 30 seconds you should
hear the outdoor fan motor stop and then restart. This is the 2nd
compressor starting up. If you don’t hear the stop and start of the
outdoor fan then there is a problem.
NOTE: THE LAST 2 TESTS CAN BE CONDUCTED IN THE HEATING MODES ALSO.